Rational Use of FPFRC in Slab-Connections Under Reversed Horizontal Cyclic Loading

Citation:
Ramos, A, Isufi B, Marreiros R, Bolesova M, Gajdsova K.  2022.  Rational Use of FPFRC in Slab-Connections Under Reversed Horizontal Cyclic Loading. Engineering Structures. Accepted for publication

Abstract:

Slab – column connections that are subjected to combined gravity and horizontal loading during an earthquake are prone to premature failure due to punching shear. Traditional solutions to avoid punching failure and to increase the displacement capacity of this type of connection include using stirrups and double-headed studs as shear reinforcement. The use of High-Performance Fiber Reinforced Concrete (HPFRC) in a small region of the slab around the column as a substitute for traditional solutions is investigated in this paper, because this material has the potential to reduce labor and material costs. To fulfill this objective, four slab specimens with a thickness of 150 mm were tested under combined gravity and reversed horizontal drifts. The results are discussed in detail. The experimental variables considered were the top flexural reinforcement ratio, the size of the HPFRC zone and the intensity of the gravity load. Previously published tests that serve as reference specimens are used to compare the results. The behavior of the specimens with HPFRC was substantially improved compared to the reference specimens in terms of drift capacity: from only 1.0% drift to above 5.5%, even though a very small quantity of HPFRC was used, extended up to only 1.5 times the effective depth of the slab from the face of the column. Specimens with HPFRC also behaved better when compared to specimens with High-Strength Concrete (HSC). Side effects of using HPFRC in the slab in the vicinity of the column include an increase of the unbalanced moment transfer capacity and lateral stiffness, as well as a reduction of the deflections of the slab.